Directions for use:
1. Drain the used coolant (water or antifreeze) from the system, then flush it with clean running water. If the contamination is significant, flush until the drained water runs clear.
2. Prepare the working solution: mix 10 liters of UNIVERSAL SANFIX reagent with 50 liters of water.
3. Pour the resulting solution into the system and flush:
- Maintain the temperature no higher than 60°C
- Flush for 3-4 hours
- Ensure free release of carbon dioxide released during the process by venting the system to the atmosphere.
4. Drain the used solution, then thoroughly flush the system with clean water.
5. If necessary, repeat the procedure (steps 2-4). The repeat flush parameters remain the same.
Precautions:
Wear protective equipment for hands, eyes, and upper respiratory tract. If the reagent comes into contact with skin, rinse with plenty of water and apply petroleum jelly.
Storage: Store reagents out of the reach of children, in a tightly sealed container, at temperatures above 0°C. Avoid direct sunlight at temperatures above 0°C.
Other characteristics:
Hazard level of the chemical product as a whole: Highly hazardous product with respect to its impact on the body - hazard class 2 in accordance with GOST 12.1.007-762.
General fire and explosion hazard characteristics: Non-flammable liquid.
Recommendations for safe handling and transportation: The product is transported by all modes of transport in accordance with the regulations for the transportation of dangerous goods.
Pour into white canisters (not transparent); additional film protection is not required, but do not store in direct sunlight!